1. Malaysia
  2. All 3M Products
  3. Electrical
  4. Power Cable Connectors
  5. Power Cable Terminations
  6. 3M™ Cold Shrink QT-III Termination Kit 7653-T-150, CN, JCN Cable, 5-35 kV, Insulation OD 0.72-1.29 in, 1/kit, Indoor

3M™ Cold Shrink QT-III Termination Kit 7653-T-150, CN, JCN Cable, 5-35 kV, Insulation OD 0.72-1.29 in, 1/kit, Indoor

  • 3M ID 7000140704

Provides a void-free seal to jacketed concentric neutral and concentric neutral power cables

High dielectric-constant material regulates the distribution of electric field stress

Suitable for indoor applications

View more details

Details

Highlights
  • Provides a void-free seal to jacketed concentric neutral and concentric neutral power cables
  • High dielectric-constant material regulates the distribution of electric field stress
  • Suitable for indoor applications
  • Termination has 0.72 to 1.29-in insulation O.D
  • Accommodates wire sizes of 300 to 500 kcmil at 5kV, 250 to 500 kcmil at 8 kV, 2/0 AWG to 300 kcmil at 15kV, 2 to 4/0 AWG at 25/28 kV, 2 to 2/0 AWG at 35kV
  • Non-tracking, silicone rubber insulation offers durability
  • Withstands voltages of 5 to 35kV and is 150 kV BIL-rated
  • Includes a non-skirted, 1-piece, cold shrink termination
  • IEEE Standard 48 Class 1 Approved for indoor and weather-protected applications

3M™ Cold Shrink QT-III 7640-T & 7650-T Series Termination Kit includes a non-skirted, 1-piece termination. It ensures a pliable, tight seal for jacketed concentric neutral and concentric neutral power cables. The conjunction of high dielectric-constant material and silicone rubber insulation allows the termination to withstand voltages of 5 to 35kV.

3M™ Cold Shrink QT-III 7640-T & 7650-T Series Termination Kit is designed for terminating medium voltage cables. The track-resistant, silicone rubber insulation of the termination has a hydrophobic property and offers a long-lasting service life. The lower surface stress, high dielectric-constant material offers an optimized BIL performance while ensuring a leak-proof, compact fit. IEEE Standard 48 Class 1 Approved for indoor and weather-protected applications. Conductor Size Range for · 5 kV: 300-500 kcmil · 8 kV: 250-500 kcmil · 15 kV: 2/0 AWG-300 kcmil · 25/28 kV: 2-4/0 AWG · 35 kV: 2-2/0 AWG This termination is compatible with the following lugs: QL2-A-2-250, for conductor range: 2/0 AWG-250 kcmil (15kV), 2-4/0 AWG (25/28kV), 1/0-2/0 AWG (35kV)

Typical Properties