  6. 3M™ Cold Shrink QT-II Indoor Termination Kit 5621K, Tape, Wire and UniShield®, 5-8 kV, 0.32-0.46 in (8-12 mm) Cable Insul. O.D., 3 terminations/kit

3M™ Cold Shrink QT-II Indoor Termination Kit 5621K, Tape, Wire and UniShield®, 5-8 kV, 0.32-0.46 in (8-12 mm) Cable Insul. O.D., 3 terminations/kit

  • 3M ID 7000005934

Provides a void-free seal to tape shield, wire shield and UniShield® power cables

High dielectric-constant material regulates the distribution of electric field stress

Suitable for indoor applications

View more details

Details

Highlights
  • Provides a void-free seal to tape shield, wire shield and UniShield® power cables
  • High dielectric-constant material regulates the distribution of electric field stress
  • Suitable for indoor applications
  • Termination has 0.32 to 0.46-in insulation O.D
  • Accommodates wire sizes of 8 to 4 AWG at 5kV 100%, 8 to 6 AWG at 5kV 133%/8 kV 100%, 8 AWG at 8 kV 133%
  • Non-tracking, molded, silicone rubber insulation offers durability
  • Withstands voltages of 5 to 15kV and is 110 kV BIL-rated
  • Includes three 1-piece, single-phase, cold shrink terminations
  • IEEE Standard 48 Class 1 Approved for weather-protected applications

3M™ Cold Shrink QT-II 5620K Series Termination Kit includes three 1-piece, non-skirted single-phase terminations. It ensures a pliable, tight seal for tape shield, wire shield and UniShield® power cables. The conjunction of high dielectric-constant material and silicone rubber insulation allows the termination to withstand voltages of 5 to 15kV.

3M™ Cold Shrink QT-II 5620K Series Termination Kit is designed for terminating medium voltage, solid dielectric-shielded cables in indoor applications. When the terminal's core is unwound, it shrinks over the cable and ensures a leak-proof, ideal fit. The track-resistant, silicone rubber insulation of the termination offers a long-lasting service life. IEEE Standard 48 Class 1 Approved for weather-protected applications. Conductor Size Range for · 5 kV (100%): 8-4 AWG · 5 kV (133%): 8-6 AWG · 8 kV (100%): 8-6 AWG · 8 kV (133%): 8 AWG

Typical Properties